我区新到一台西安产的KGCA-90/50~90-KB充电机,安装在斜井充电硐室,使用不久,即发生两起故障,现将这两次故障的检修情况介绍如下: 一、合隔离器GK时总开关跳闸,经检查发现是由于GK的A相动刀片松动滑到钢质连接杆上造成A相接地所致,动刀片松动的原因在于动刀片的固定螺丝上没有加锁紧螺帽,经长途运输后松动了。处理时由于GK设计紧凑、空间小,正面伸不进手,不好操作,为此将U形螺丝反装在动刀片上套进连接杆里,用M6螺帽拧紧并加锁紧螺帽锁紧,这样既可防止再松动,也便于日后修理。厂家原在钢质方形连接杆上缠有1mm厚的4层绝缘布,但缠得不均匀,边上成梯
The newly arrived KGCA-90/50 ~ 90-KB charger from Xi’an was installed in the inclined chamber and used in two shortcomings. Now, the maintenance of these two faults are introduced as follows: First, the total switch GK switch tripping, the inspection found to be due to GK’s A-phase moving blade loosening slide to the steel connecting rod caused by A-phase ground, moving blade loose because the fixed blade screw Did not add a locking nut, loose after long-distance transport. GK due to the design process compact, small space, the front stretch did not enter, not good for this purpose, the U-shaped screw mounted on the moving blade into the connecting rod, with M6 nut tighten and add the lock nut lock Tight, so as to prevent further loosening, but also easy to repair in the future. The original manufacturer of steel square connecting rod wrapped 1mm thick 4 layers of insulating cloth, but wrapped unevenly, the edge of the ladder