1999年4月25日晚,山西省临猗县城西10千伏线路接地掉闸。经查找,是张庄支线~#6杆C相线断。 ~#6杆使用瓷横担,螺栓由上往下穿入,由于年长日久,铝线摆动引起瓷担振动,螺母自动松开。恰巧晚上刮大风,铝线摆动剧烈,引起螺母松掉落地,瓷担连同螺杆脱落碰杆,铝线烧断落地引起掉闸。 事故原因分析及措施 (1)螺栓穿向错误。《农村低压电力技术规程》规定:螺栓穿入方向:顺线路者由电源方向穿入,横线路者由左向右穿(面向受电侧),垂直地面由下向上穿。
On the evening of April 25, 1999, the 10 kV line west of Linqu County in Shanxi Province was grounded. The search is Zhangzhuang Extension ~ # 6 C-phase off. ~ # 6 using cross-arm porcelain, bolts penetrate from top to bottom, due to age, aluminum vibration caused by vibration porcelain, nuts automatically release. It happens to be a strong wind at night, aluminum swing violently, causing the nut loose landing, porcelain bear with the screw off the rod, aluminum wire burned off the gate. Causes of the accident analysis and measures (1) bolt through the wrong. “Rural low-voltage power technical regulations” provides: Bolt penetrating direction: Shun line by the direction of the power into the horizontal line from left to right (facing the receiving side), the vertical ground from the bottom to wear.