一、常见故障及解决办法1.无流量通过时有信号输出(1)表壳、系统未接地或接地不良而引入干扰信号。解决办法:检定前应确保表壳及系统接地良好,且使用专用信号线或者符合替代要求的信号线,并检查接地电阻,要求不大于10Ω,否则重新处理接地。(2)管道振动大。解决办法:最直接的检测方法是用手感觉管道的振动。可以采用外部机械消振措施,如用橡胶软接头消振。另外,很多厂家在设计涡街流量计时也考虑防震的需求,调整参数也可以减轻振动
First, the common faults and solutions 1. There is no signal flow through the output (1) case, the system is not grounded or bad ground and the introduction of interference signals. Solution: Ensure that the case and system are properly grounded before using the signal. Use a dedicated signal line or a signal line that meets the requirements of the alternative. Check the grounding resistance and the requirement is not more than 10Ω. Otherwise, re-process the grounding. (2) pipeline vibration. The solution: The most direct detection method is to feel the vibration of the pipe by hand. External mechanical damping measures can be used, such as using rubber soft vibration absorber. In addition, many manufacturers in the design of vortex flowmeter also consider the need for shockproof, adjust the parameters can also reduce vibration