我国规范关于数据中心供配电系统的要求包括。(1)A级数据中心A级数据中心按一级特别重要负荷供电,具体要求:①市政电源系统:两路市电供电。两路电源不应同时受到损坏;变压器M(1+1)冗余。②后备柴油发电机系统:后备柴油发电机N或(N+X)冗余;柴油发电机储油量72h。③UPS不间断电源系统:UPS不间断电源系统按2N或2(N+1)冗余配置;UPS系统电源蓄电池备用时间
China’s norms on the data center for power distribution system requirements include. (1) A-level data center A-class data center according to a particularly important load power supply, the specific requirements: ① municipal power system: two-way mains supply. Two power supply should not be damaged at the same time; Transformer M (1 +1) redundancy. ② backup diesel generator system: backup diesel generator N or (N + X) redundancy; diesel generator storage capacity 72h. UPS uninterruptible power supply system: UPS uninterruptible power supply system by 2N or 2 (N + 1) redundant configuration; UPS system power battery backup time