今年我参加数台发生缺水事故锅炉的检查,其中两例缺水事故的原因带有一定的普遍性,现将检查及分析情况介绍于下: 1 事故经过及检查情况 1991年1月20日,某厂(简称甲厂,下同)一台14吨/时的SZF14——13型沸腾锅炉在5点时点火开炉。启动时水位偏高。5点40分锅炉升压至0.3MPa并投入运行。此时炉顶后部水位表已看不见水位,操作人员认为是满水,就打开给水回水管的阀门,使锅炉停止了进水。由于控制室内低地水位计失效,操作人员只能在控制室外远远观看炉顶后部的就地水位表。至6
This year I participated in the inspection of several boilers that experienced water shortages. The causes of the two cases of water shortages are somewhat generalized. The inspection and analysis are now introduced as follows: 1. The Accident and the Checks January 20, 1991 , A plant (referred to as a plant, the same below) a 14 tons / hour SZF14-13 type boil-off boiler at 5:00 when the ignition furnace. High water level when starting. 5:40 boiler booster to 0.3MPa and put into operation. At this point the water level behind the furnace roof has been invisible, the operator that is full of water, open the water return pipe valve, the boiler stopped water. Due to the failure of the control indoor low water level gauge, the operator can only watch the local water level gauge in the back of the furnace roof outside the control room. To 6